Part No. PC10001
PC10002
PC10003
The NEON Conventional Fire Alarm Panel is an advanced and reliable fire detection and notification system designed for various applications. Available in two, four, and eight zone variants, this panel offers scalable solutions to meet the specific needs of different environments.
Featuring state-of-the-art technology, the NEON Conventional Fire Alarm Panel ensures early and accurate detection of fire incidents. The two-zone variant is suitable for smaller spaces, while the four and eight-zone options provide expanded coverage for larger areas. This flexibility makes the NEON panel suitable for a wide range of settings, including commercial buildings, industrial facilities, and residential complexes.
Product Specification
Maximum number of detectors per zone: 20
Notification appliances current: 4 x 400mA (total maximum current 1Amp)
Mains power: 230V AC 50/60Hz
Zones input voltage (with EOL & AEOL): 16 to 21V
Maximum input power: 100VA max input power (0.5Amp)
Battery replacement: 2 x 12V 7Ah VRLA batteries will fit in the panel
Standy power: 5 VA (25mA)
Auxiliary power outputs: 24V DC 1Amp total ('AUX'+'AUX R')
Zone termination: 4.7KΩ 5% 1/2W resistors or 22µF / 25V eletrolytic capacitors
Monitored output termination: 4.7KΩ resistors 5% 1/2W
Fire relay output: Dry contacts NO or NC selectable. 50V / 1.5A max (DC or AC)
Fault relay output: Dry contacts NO or NC selectable. 50V / 1.5A max (DC or AC)
Environmental: Temperature: -2 to 45˚C (32 to 120˚F), Humidity: 5 to 95% RH, non condensing
Panel dimensions (HxWxD) [mm]: 315 x 425 x 105 mm. In a semi flush wall mounting extruding depth: 25mm
Weight (without the batteries): 2.8g
Key Features
Conventional Fire Alarm Panel
2, 4 or 8 Zones
Code or Key Entry
Constant or ANSI sound output patterns
Universal Access Level 2 key (key code access as well)
4 Sounder Circuits
Takes 7AH batteries
24VDC Auxiliary output
24VDC output, interruptible during reset (eg. for gas detector reset)
Remote reset input
Bell (clash change) input
Walk test (individual zone capable) (EN54-2 §10 certified)
Output delays
Active End of Line Monitored Zones
Alarm verification with pre-alarm output. Configurable for each zone. 7 delay values (EN54-2 §7.12 certified).
Day/Night operation (with external timer)
Cross zone (dual zone) alarms. Configurable on each zone pair (4 pairs on 8 zone model)
Repeater expansion port (connection to optional RS485 expansion module)
TCP/IP module expansion port
Optional TCP/IP module for connectivity to SmartView software
Alarm and Fault/Disablement indicators for each zone
コメント